High-rise residential blocks
Towers of 18 metres or seven storeys and more, with duties stacked on top of the Fire Safety Order.
- Written report to keep on file
- Clear action plan, highest risk first
- Price agreed before booking
A residential building in England that is at least 18 metres high or has at least seven storeys, with at least two homes, is a higher-risk building under the Building Safety Act 2022. It must be registered with the Building Safety Regulator, and it has an accountable person responsible for managing building safety risks in the parts they control.
The fire risk assessment under the Fire Safety Order still has to be done as well. The responsible person for it and the accountable person are often the same organisation, but not always, and since October 2023 they have had to cooperate.

What the Fire Safety (England) Regulations 2022 add
For buildings of 18 metres or seven storeys and more: a secure information box for the fire service, wayfinding signs on the stairs and landings, floor plans and building plans shared with the fire and rescue service, information about the external walls, and monthly checks of lifts for firefighters and of key firefighting equipment, with faults that cannot be fixed within 24 hours reported to the fire and rescue service. For buildings over 11 metres, communal fire doors must be checked every three months, and flat entrance doors every year on a best-endeavours basis.
Most purpose-built residential towers were designed for a stay-put strategy, which relies on each flat holding a fire. Where the walls, floors or doors may not do that, the strategy may need to change, and residents must be told.
Towers are priced from the floor area and the number of storeys.
Send us the postcode, what the building is and how many floors it has. We will send a written price.